top of page

Shelton State Community College

Updated: Oct 15

Continuous Commissioning® Services

SEA helped reduce utility costs by $387k in less than a year.


About the Facility

Shelton State Community College is a public community college in Tuscaloosa, Alabama operated by the Alabama State Department of Postsecondary Education. Shelton is one of the largest two year colleges in the state. SEA was tasked to improve the performance of building operations systems through Continuous Commissioning® on the Martin Campus. The project involved evaluation and optimization of the Heating, Ventilation and Air Conditioning (HVAC) units.

AT A GLANCE

Shelton State Facts

  • $387k Reduced utility costs in less than a year

  • 8 Commissioned Buildings

  • 655k Square Feet

  • 2016 Completion Date


Recommended Solutions

The documented utility savings resulted from optimizing HVAC equipment accordingly:

  1. Optimized hot water supply temperature to reduce boiler demand while maintaining heating needs

  2. Programmed control strategies to reduce/eliminate dehumidification based on space requirements

  3. Programmed air handling units to reset the supply air temperature based on space temperature and setpoint

  4. Monitored zone reheat valves to determine overcooled areas, verified flow rates versus design, making necessary corrections

  5. Modified terminal box flow rates to reduce the amount of unoccupied cooling and heating

  6. Investigated leaking or opened preheat valves on air handling units and manually closed valves on units

  7. Built air handling unit schedules to shut down when unoccupied and to restart if spaces required conditioning

  8. Verified outside air and return air damper operation on air handling units

  9. Examined chilled water valves for leakage when commanded closed


Documented Savings

In just four months, the savings had already surpassed the projected annual goal of $85,000 and continued to grow with ongoing maintenance and careful oversight of the system. The documented savings for ten months was $387,144 and aggregate savings at the end of the SEA agreement were $663,144 which is 10,810,384 kWh.

2 views

Recent Posts

See All

Comments


bottom of page